Product Details
High Accuracy Grade of 0.01 Stationary Single-Phase Reference Standard Meter
GENY’s reference standards adopt unique sampling technology, with high accuracy, wide testing range. They are suited for electric power utilities, energy meter manufactures, measuring and quality examining departments using as standards.
SZ-01A-K3E wide-range standard meter uses the newest electric technical in the world. The core of SZ-01A-K3E is high-speed DSP、CPLD and MCU, it has the high-speed A/D converter with self-calibration at the same time. It can sample AC signal in high speed and deal with it in special way by DSP, this makes the circuit much simpler. It can calculate and measure AC signal exactly.

High accuracy up to 0.01%
High stability
Wide testing range
Multiple function, measuring voltage, current, phase, frequency, power, energy etc.,
Large size LCD display screen
With communication port to PC
MODEL |
SZ0A1-K3E |
Standard conditions |
Temperature of environment: 20℃ ± 2℃
Relative humidity: 60 % ± 15 %
Supply power: voltage 220V ± 22V
frequency 50Hz ± 2Hz
Magnetic intensity: ≤0.025mT
Warm-up: the time of warm-up ≥ 90minute
|
Rating current |
0.001A、0.01A、0.1A、1A (1A input port on the rear board)
10A (10A input port on the rear board)
100A (100A input port on the rear board)
Imax = 160A
|
Ratio voltage |
50V、100V、200V、400V Umax = 480V
|
Precesion |
|
current |
± 0.01%RD 10mA~120A
± 0.03%RD 1mA~10mA
|
Volage |
± 0.01%RD 50V~400V
± 0.05%RD 5V~50V
|
|
Power
|
Active power:
± 0.01%RD (50V~400V,0.05A~120A , cosφ≥0.5)
± 0.05%RD (50V~400V,0.001A~0.05A , cosφ≥0.5) Reactive power:
± 0.01%RD (50V~400V,0.05A~120A , sinφ=1.0)
± 0.01%RD (50V~400V,0.05A~120A , sinφ=0.5L/0.8C)
|
energy |
Active energy:
± 0.01%RD (50V~400V,0.05A~120A , cosφ≥0.5)
± 0.05%RD (50V~400V,0.001A~0.05A , cosφ≥0.5) Reactive energy:
± 0.01%RD (50V~400V,0.05A~120A , sinφ=1.0)
± 0.05%RD (50V~400V,0.05A~120A , sinφ=0.5L/0.8C)
|
Power factor |
Range of measurement: 0~± 1.000000
Precision: ± 0.001%RD(cosφ ≥ 0.5)
|
phase |
Range of measurement: 0°~360°
Precision: 0.003° (U≥50V, I≥0.05A)
|
Frequency |
Range of measurement: 45Hz~65Hz
Precision: ± 0.0002%RD (U≥50V)
|
Pulse Output |
TTL level
load ability > 2kΩ
|
Constant |
CH=1012 imp/kW·h (imp/kvar·h) (0~0.001A )
CH=1011 imp/kW·h(imp/kvar·h) (0.001~0.01A)
CH=1010 imp/kW·h(imp/kvar·h) (0.01~0.1A)
CH=109 imp/kW·h(imp/kvar·h) (0.1~1A)
CH=108 imp/kW·h(imp/kvar·h) (1~10A)
CH=107 imp/kW·h(imp/kvar·h) (10~100A)
CL= CH / 50000 imp/kW·h(imp/kvar·h)
|
Use condition |
Surrounding temperature: 5 ℃~40 ℃
Relative humidity: 35%~85%
|
Temperature affection |
(5 ℃~40 ) ℃
Voltage, current and frequency ≤ ±2ppm/ ℃
Power ≤ ±5ppm/ ℃
|
Communication port |
RS-232
RS-485 (use for manufacturer calibration)
|
Power supply |
Voltage: AC220V ± 22V
Frequency: 50Hz ± 2Hz
Power consumption: 45VA(max)
|
Dimension |
W×H×D = 325mm×109mm×288mm
|
Weight |
5.5kg
|
High quality product
High stability
Friendly user interface
Convenient operation
-
Long time warranty
1. Wiring of 1A range
2. Wiring of 10A range

3. Wiring of 100A range